Home /Drop Out Fuses / 100 A Fuse Cutout
Baocheng Electrical
100 A Fuse Cutout
RW7-10/100
The RW7-10/100 is a 10 kV, 100 A outdoor expulsion fuse cutout with a porcelain insulating support. It protects overhead lines and distribution transformers against overloads and short circuits.
10 kV rated voltage · 50 Hz system
100 A rated current · 30–100 MVA interrupting capacity
1-minute power-frequency withstand voltage: 42 kV dry / 34 kV wet

Electrical Characteristics
Rated voltage
10 kV
Rated current
100 A
Interrupting capacity
30–100 MVA
System frequency
50 Hz
What Is the 100 A Fuse Cutout?
The cutout protects lines and transformers against overloads and short circuits. Its base supports the contacts and arc-extinguishing assembly.
A rotating spring support at the lower end keeps the fuse link under tension and helps retain the fuse tube in its closed position.
The RW7-10 family also includes a 200 A version. The specifications below apply to the /100 model.
Technical Specifications & Selection Data
| Parameter | RW7-10/100 |
|---|---|
| Electrical ratings | |
| Rated voltage | 10 kV |
| Rated current | 100 A |
| System frequency | 50 Hz |
| Interrupting capacity (lower / upper limit) | 30 / 100 MVA |
| Insulation levels | |
| Dry power-frequency withstand voltage (1 min) | 42 kV rms |
| Wet power-frequency withstand voltage (1 min) | 34 kV rms |
| Service conditions | |
| Ambient temperature | −30 to +40 °C |
| Maximum altitude | 1,000 m |
| Maximum wind speed | 35 m/s |
The model table gives interrupting capacity in MVA. The dry and wet withstand values are rms voltages for a one-minute test.
Design & Operating Principle
Reading the Model Designation
![]() | ||
![]() | Rated current (A) | |
![]() | Rated voltage (kV) | |
![]() | Design series | |
![]() | Outdoor service | |
![]() | Fuse | |
![]() | Optional composite support prefix |
RW7-10/100 · Model designation
RW7-10/100 has a porcelain support. An H prefix in the family designation identifies a composite support.
Closed position
The lower spring support maintains tension on the fuse link.
Fuse operation
During an overload or short circuit, the fuse element melts and the link is rapidly withdrawn from the tube.
Arc extinction
The tube uses staged venting to interrupt currents of different magnitudes.
Load-switching duty
The family overview mentions switching rated load current. Obtain the applicable switching rating and operating instructions for the ordered configuration.
Contact Assembly & Porcelain Support
The photographs show the contact hardware and the porcelain insulating support described in the RW7-10 manual.
Upper contact assembly
The rain cover and spring are made of thickened stainless steel.
The connecting plate and fuse-tube cap are copper.
Porcelain insulating support
The ribbed porcelain post supports the cutout hardware.
The manual identifies fired high-voltage porcelain as the insulating material.
Applications, Features & Selection Considerations
Check the installation site against the service limits before selecting the cutout.
Line protection
Overload and short-circuit protection for overhead lines.
Transformer protection
Select the fuse link to coordinate with the protected transformer.
Porcelain insulation
The RW7-10/100 uses a porcelain support for outdoor service.
Mechanical environment
Use in locations free from severe vibration or impact.
Atmospheric conditions
Exclude fire or explosion hazards, chemically aggressive gases, heavy atmospheric pollution and salt mist.
Technical Documents & Supply Scope
100 A Fuse Cutout Technical Documents
Request the technical package for the selected configuration:
- Model-specific data sheet
- Mounting and terminal drawing
- Fuse-link characteristics
Inspection & Test Documentation
Request the approved data sheet, insulation and breaking-duty test evidence, and inspection records for the exact cutout and fuse-link combination. Check the tested model, configuration and report scope.
Confirm the dry and wet one-minute withstand levels for the specified assembly.
Supply Scope to Confirm
- RW7-10/100 cutout quantity
- Fuse-link selection and spares
- Mounting hardware and terminals
Confirm accessories and quantities in the quotation.
Installation & Maintenance Review
Verify mounting dimensions, terminal connections and service clearances against the approved installation drawing.
Send the network voltage and earthing arrangement, required cutout rating, load and fault current, fuse-link requirements, site conditions, mounting details and quantity with your inquiry.
100 A Fuse Cutout FAQ
What voltage is the RW7-10/100 rated for?
The model table specifies 10 kV.
What interrupting capacity is listed?
The 100 A model has a lower limit of 30 MVA and an upper limit of 100 MVA.
Which support material does this model use?
RW7-10/100 has a porcelain support. H denotes a composite support in the family code.
What are the dry and wet withstand voltages?
The one-minute power-frequency withstand voltages are 42 kV rms dry and 34 kV rms wet.
What are the altitude and wind limits?
The maximum altitude is 1000 m and the maximum wind speed is 35 m/s.
What is the ambient temperature range?
The service range is −30 °C to +40 °C.