Home /Drop Out Fuses / 100 A Fuse Cutout

Baocheng Electrical

100 A Fuse Cutout
RW7-10/100

The RW7-10/100 is a 10 kV, 100 A outdoor expulsion fuse cutout with a porcelain insulating support. It protects overhead lines and distribution transformers against overloads and short circuits.

10 kV rated voltage · 50 Hz system

100 A rated current · 30–100 MVA interrupting capacity

1-minute power-frequency withstand voltage: 42 kV dry / 34 kV wet

Electrical Characteristics

Rated voltage

10 kV

Rated current

100 A

Interrupting capacity

30–100 MVA

System frequency

50 Hz

What Is the 100 A Fuse Cutout?

The cutout protects lines and transformers against overloads and short circuits. Its base supports the contacts and arc-extinguishing assembly.

A rotating spring support at the lower end keeps the fuse link under tension and helps retain the fuse tube in its closed position.

The RW7-10 family also includes a 200 A version. The specifications below apply to the /100 model.

Technical Specifications & Selection Data

ParameterRW7-10/100
Electrical ratings
Rated voltage10 kV
Rated current100 A
System frequency50 Hz
Interrupting capacity (lower / upper limit)30 / 100 MVA
Insulation levels
Dry power-frequency withstand voltage (1 min)42 kV rms
Wet power-frequency withstand voltage (1 min)34 kV rms
Service conditions
Ambient temperature−30 to +40 °C
Maximum altitude1,000 m
Maximum wind speed35 m/s

The model table gives interrupting capacity in MVA. The dry and wet withstand values are rms voltages for a one-minute test.

Design & Operating Principle

Reading the Model Designation

Optional H, R, W, 7, 10, 100
Rated current (A)
Rated voltage (kV)
Design series
Outdoor service
Fuse
Optional composite support prefix

RW7-10/100 · Model designation

RW7-10/100 has a porcelain support. An H prefix in the family designation identifies a composite support.

Closed position

The lower spring support maintains tension on the fuse link.

Fuse operation

During an overload or short circuit, the fuse element melts and the link is rapidly withdrawn from the tube.

Arc extinction

The tube uses staged venting to interrupt currents of different magnitudes.

Load-switching duty

The family overview mentions switching rated load current. Obtain the applicable switching rating and operating instructions for the ordered configuration.

Contact Assembly & Porcelain Support

The photographs show the contact hardware and the porcelain insulating support described in the RW7-10 manual.

Upper contact assembly

The rain cover and spring are made of thickened stainless steel.

The connecting plate and fuse-tube cap are copper.

Porcelain insulating support

The ribbed porcelain post supports the cutout hardware.

The manual identifies fired high-voltage porcelain as the insulating material.

Applications, Features & Selection Considerations

Check the installation site against the service limits before selecting the cutout.

Line protection

Overload and short-circuit protection for overhead lines.

Transformer protection

Select the fuse link to coordinate with the protected transformer.

Porcelain insulation

The RW7-10/100 uses a porcelain support for outdoor service.

Mechanical environment

Use in locations free from severe vibration or impact.

Atmospheric conditions

Exclude fire or explosion hazards, chemically aggressive gases, heavy atmospheric pollution and salt mist.

Technical Documents & Supply Scope

100 A Fuse Cutout Technical Documents

Request the technical package for the selected configuration:

  • Model-specific data sheet
  • Mounting and terminal drawing
  • Fuse-link characteristics

Inspection & Test Documentation

Request the approved data sheet, insulation and breaking-duty test evidence, and inspection records for the exact cutout and fuse-link combination. Check the tested model, configuration and report scope.

Confirm the dry and wet one-minute withstand levels for the specified assembly.

Supply Scope to Confirm

  • RW7-10/100 cutout quantity
  • Fuse-link selection and spares
  • Mounting hardware and terminals

Confirm accessories and quantities in the quotation.

Installation & Maintenance Review

Verify mounting dimensions, terminal connections and service clearances against the approved installation drawing.

Send the network voltage and earthing arrangement, required cutout rating, load and fault current, fuse-link requirements, site conditions, mounting details and quantity with your inquiry.

100 A Fuse Cutout FAQ

The model table specifies 10 kV.

The 100 A model has a lower limit of 30 MVA and an upper limit of 100 MVA.

RW7-10/100 has a porcelain support. H denotes a composite support in the family code.

The one-minute power-frequency withstand voltages are 42 kV rms dry and 34 kV rms wet.

The maximum altitude is 1000 m and the maximum wind speed is 35 m/s.

The service range is −30 °C to +40 °C.

Related Products

Explore related drop out fuses and fuse cutouts for overhead distribution and transformer protection applications.