VCB Breaker
ZW32-40.5

Outdoor vacuum interruption for 35 kV power systems. The supplied ZW32-40.5 manual describes a spring-operated breaker for pole-mounted or substation arrangements, with configurable current transformers and optional recloser control.

40.5 kV · 630 / 1250 / 1600 A · 25 kA | Outdoor vacuum switching

33KV VCB Breaker

Electrical Characteristics

Nominal system voltage

35 kV

Rated voltage

40.5 kV

Rated normal current

630 / 1250 / 1600 A

Rated short-circuit breaking current

25 kA

About the ZW32-40.5

The document body identifies the equipment as ZW32-40.5, with a 40.5 kV rated voltage for 35 kV network applications. A spring mechanism operates the vacuum interrupters, while optional control equipment supports feeder protection and automatic reclosing.

The source filename says ZW32-33, but the manual body says ZW32-40.5. This page follows the body data and requires confirmation of the commercial model designation.

Technical review draft: confirm the filename/model discrepancy, homepage rating differences and selected installation drawing before publication or ordering.

Technical Specifications — ZW32-40.5

Electrical ratings — manual p. 2

No.ParameterUnitValue / condition
1Rated voltagekV40.5
2Rated normal currentA630 / 1250 / 1600
3Rated frequency, table entryHz50 / 60; application text describes 50
4Rated short-circuit breaking currentkA25
5Rated short-circuit making currentkA peak80
6Rated peak withstand currentkA peak80
7Rated short-time withstand currentkA31.5
8Rated duration of short circuits4

Insulation — manual p. 2

No.ParameterUnitValue / condition
1Power-frequency withstand, wet / drykV80 / 95
2Lightning impulse withstandkV peak185
3Secondary circuit withstandkV2

Mechanical characteristics — manual p. 2

No.ParameterUnitValue / condition
1Mechanical enduranceoperations20000
2Rated short-circuit interruptionsoperations30
3Closing timems25–45
4Opening timems20–45
5Contact gapmm16 ± 1
6Contact overtravelmm4 ± 0.5
7Mass, table entrykg295

Control and sensing — manual pp. 1–3

No.ParameterUnitValue / condition
1Operating mechanism—Spring stored-energy
2Control voltage, table entry—220 V DC
3Current transformers—2 or 3; configuration to confirm
4Recloser controller—Optional
5Voltage-transformer supply—Optional; configuration to confirm

Installation and site confirmation

No.ParameterUnitValue / condition
1Mounting variants—Pole-mounted / substation drawings
2Phase spacing—Different arrangements shown; use approved drawing
3Ambient and altitude limits—Not established by supplied operating data
4Commercial model designation—Filename ZW32-33 / body ZW32-40.5

ZW32-40.5: Design & Operating Principle

Breaker Assembly — Manual Detail

Isometric detail extracted from manual p. 5. Use the approved arrangement for the ordered unit.

The enclosure supports three insulated poles and the operating mechanism. Current-transformer and controller options depend on the selected configuration.

01 Store Operating Energy

The spring mechanism stores the energy required for breaker operation. Confirm the available control supply and charging arrangement.

02 Operate the Contacts

A close or trip command releases the corresponding mechanism action and drives the interrupter contacts through the linkage.

03 Clear the Fault

The manual lists a 25 kA short-circuit breaking rating. Its separate 31.5 kA short-time withstand value is not the breaking rating.

Optional Protection Package

Current transformers and an optional recloser controller support protection and monitoring. Confirm the controller, CT ratios and auxiliary-power equipment together.

Drawings & Installation Interfaces

Review the supplied drawings for the selected arrangement. Select an image to inspect the full-size original; confirm the approved project revision before installation.

Breaker Body — General Arrangement

Front, side and plan views
Terminal and fixing details shown
Original manual geometry retained
Select the applicable variant

The upper drawings on manual p. 5 show the breaker body and its fixing interface. The manual includes differing phase spacings across arrangements; do not combine dimensions from different versions.

Substation Mounting — Support Arrangement

Breaker and support structure
Front and side installation views
Control enclosure shown
Approved civil interface required

The lower drawing on manual p. 5 illustrates a substation mounting arrangement. Confirm support dimensions, foundation details and the selected breaker variant before civil works.

Applications, Features & Procurement Considerations

The document body identifies the equipment as ZW32-40.5, with a 40.5 kV rated voltage for 35 kV network applications. A spring mechanism operates the vacuum interrupters, while optional control equipment supports feeder protection and automatic reclosing.

35 kV System Application

The manual body pairs a 35 kV network application with a 40.5 kV equipment rating.

Spring Mechanism

Stored energy operates the vacuum interrupter contacts.

Optional Recloser Control

The controller option supports an application-specific protection and reclosing scheme.

Current-Transformer Selection

Choose ratios and arrangement for the required measurement and protection duties.

Mounting Alternatives

The manual provides both pole-mounted and substation installation references.

Technical Documents & Supply Scope

ZW32-40.5 Technical Documents

Request the technical package for the selected configuration:

  • Approved electrical ratings and model designation.
  • General arrangement and mounting drawings.
  • Controller wiring and current/voltage sensing details.
  • Installation and maintenance instructions.

Inspection & Test Documentation

Request model-specific routine test records and any type-test evidence required by the project. The supplied reference manual alone does not establish certification for the offered equipment.

Agree the applicable standards, editions and evidence with the supplier. Resolve the technical-review items before approving the final data sheet.

Supply Scope to Confirm

  • Exact model, ratings and number of units.
  • Operating mechanism and auxiliary supply.
  • Current/voltage transformers and controller options.
  • Disconnectors, supports, cables and accessories.
  • Site conditions and approved installation interfaces.

Identify included and excluded equipment explicitly. Confirm that the supplied drawings and controller configuration correspond to the ordered unit.

Maintenance Planning

Prepare the inspection and maintenance plan using the instructions for the delivered assembly and its controller. Confirm operating duty, site exposure and access requirements with the supplier.

Send the network voltage, load current, prospective fault current, control supply, site conditions and required installation arrangement with your inquiry.

VCB Breaker FAQ

The filename says ZW32-33, but the manual body and model explanation identify ZW32-40.5. Confirm the final commercial designation before publication.

The manual describes 35 kV network applications with a 40.5 kV equipment rated voltage.

The manual lists 25 kA for short-circuit breaking and 31.5 kA for short-time withstand. These are different duties and must not be interchanged.

The manual contains a substation support arrangement as well as a pole-mounted installation reference. The selected structure requires approved project drawings.

It is described as an option. Confirm the controller, CT arrangement, VT supply and communication requirements in the order.

No. The manual shows different arrangements and phase spacings. Use one approved drawing set corresponding to the ordered variant.