Vacuum Circuit Breakers / 11 kV VCB Breaker

Baocheng Electrical · Technical review draft

11 kV VCB Breaker
ZW32-12

Intelligent outdoor vacuum switching for distribution feeders. The ZW32-12 combines a spring-operated breaker with current sensing and a protection controller for load switching, fault interruption and configurable automatic reclosing.

12 kV · 1250 A · 25 kA | Outdoor vacuum switching

vacuum circuit breaker price

Electrical Characteristics

Nominal system voltage

11 kV (confirm for the selected configuration)

Rated voltage

12 kV

Rated normal current

1250 A

Rated short-circuit breaking current

25 kA

About the ZW32-12

The supplied manual describes a 12 kV rated outdoor vacuum circuit breaker for three-phase 50 Hz distribution networks. Its controller supports phase overcurrent and earth-fault protection, with communication options to suit the feeder automation scheme.

The product-range title is 11 kV VCB Breaker; the equipment rated voltage in this manual is 12 kV. Confirm suitability for the actual network voltage and earthing arrangement.

Technical review draft: the manual contains inconsistent auxiliary-voltage, environmental and short-time withstand entries. The selected unit requires an approved data sheet before ordering.

Technical Specifications — ZW32-12

Electrical ratings — manual pp. 5–6

No.ParameterUnitValue / condition
1Rated voltagekV12
2Rated normal currentA1250
3Rated frequencyHz50
4Rated short-circuit breaking currentkA25
5Rated short-circuit making currentkA peak63
6Rated duration of short circuits4
7Short-time withstand currentkAConflicting entries: 20 / 25; confirm

Insulation — manual p. 5

No.ParameterUnitValue / condition
1Power-frequency withstand, dry / wet, phase to earthkV42 / 34
2Power-frequency withstand, across open contactskV48
3Lightning impulse withstand, phase to earthkV peak75
4Lightning impulse withstand, across open contactskV peak85

Mechanical characteristics — manual pp. 5–7

No.ParameterUnitValue / condition
1Mechanical enduranceoperations10000
2Closing timems20–45
3Opening timems≤ 40
4Main circuit resistanceμΩ≤ 120
5Operating mechanism—Spring stored-energy

Protection and control — manual pp. 2–3, 13–14

No.ParameterUnitValue / condition
1Protection functions—Phase overcurrent and earth fault
2Automatic reclosing—Up to 3 attempts; configurable
3Remote communication—Optional; confirm protocol and hardware
4Controller and coil supply—Confirm selected variant; manual entries differ

Service conditions — confirmation required

No.ParameterUnitValue / condition
1Breaker altitude entry, p. 5m≤ 2500
2Controller altitude entry, p. 12m≤ 2000
3Complete assembly altitude—Subject to controller and insulation selection
4Ambient temperature—Confirm; source table labels are inconsistent

ZW32-12: Design & Operating Principle

Protection Controller — Manual View

FDR-2 controller photograph from manual p. 11.

Coordinate the controller, current transformers, control cable and breaker coils as one protection package.

01 Measure & Detect

Current inputs feed the controller for phase-fault and earth-fault detection. Protection settings must be coordinated with upstream and downstream devices.

02 Trip & Reclose

The controller issues a trip command to the spring-operated breaker. Automatic reclosing is configurable and depends on the selected protection scheme.

03 Interrupt in Vacuum

Contact separation establishes an arc inside the vacuum interrupter. The arc extinguishes at current zero and the contact gap recovers its dielectric strength.

Control Interface

The manual includes FDR-2 and FDR-2GP information. Confirm controller type, connector pinout and coil supply for the supplied unit.

Drawings & Installation Interfaces

Review the supplied drawings for the selected arrangement. Select an image to inspect the full-size original; confirm the approved project revision before installation.

General Arrangement — Front & Side Views

Rated-voltage family: ZW32-12
Drawing phase centres: 340 mm
Drawing height: 720 mm
Dimensions apply to this illustrated arrangement

The manual drawing shows the breaker body and its mounting interface. Other dimensions appear elsewhere in the manual; use the approved project drawing for installation.

FDR-2GP — Controller Connections

TA and LS connector interfaces
Current-transformer inputs shown
Closing and trip coils identified
Drawing shows a 220 V AC circuit

Original controller connection diagram from the manual. Confirm the connector variant and auxiliary voltage against the delivered controller before making connections.

Applications, Features & Procurement Considerations

The supplied manual describes a 12 kV rated outdoor vacuum circuit breaker for three-phase 50 Hz distribution networks. Its controller supports phase overcurrent and earth-fault protection, with communication options to suit the feeder automation scheme.

Feeder Protection

Phase and earth-fault functions support selective protection when coordinated with the network.

Automatic Reclosing

Up to three configurable reclose attempts are described for the controller.

Current Sensing

Current-transformer selection must match the protection and measurement requirements.

Remote Monitoring

Wired or wireless communication is an option; confirm the required interface.

Spring Operation

The manual lists 10,000 mechanical operations for the breaker.

Technical Documents & Supply Scope

ZW32-12 Technical Documents

Request the technical package for the selected configuration:

  • Approved electrical ratings and model designation.
  • General arrangement and mounting drawings.
  • Controller wiring and current/voltage sensing details.
  • Installation and maintenance instructions.

Inspection & Test Documentation

Request model-specific routine test records and any type-test evidence required by the project. The supplied reference manual alone does not establish certification for the offered equipment.

Agree the applicable standards, editions and evidence with the supplier. Resolve the technical-review items before approving the final data sheet.

Supply Scope to Confirm

  • Exact model, ratings and number of units.
  • Operating mechanism and auxiliary supply.
  • Current/voltage transformers and controller options.
  • Disconnectors, supports, cables and accessories.
  • Site conditions and approved installation interfaces.

Identify included and excluded equipment explicitly. Confirm that the supplied drawings and controller configuration correspond to the ordered unit.

Maintenance Planning

Prepare the inspection and maintenance plan using the instructions for the delivered assembly and its controller. Confirm operating duty, site exposure and access requirements with the supplier.

Send the network voltage, load current, prospective fault current, control supply, site conditions and required installation arrangement with your inquiry.

11 kV VCB Breaker FAQ

11 kV is the product-range title. The supplied manual specifies a 12 kV equipment rating; network compatibility must be confirmed for the project.

The manual lists 1250 A and 25 kA short-circuit breaking current. The homepage lists a different normal current, so the offered configuration needs confirmation.

The controller description provides up to three reclose attempts with configurable delays. The final scheme depends on the network protection study.

Communication is configurable. Confirm the protocol, modem or wired interface and commissioning scope in the quotation.

The breaker table lists 2500 m, while the controller section lists 2000 m. Confirm the complete assembly rating for the site.

The manual contains different supply and coil-voltage entries. Specify the available auxiliary supply and obtain the matching approved wiring diagram.

Related Products

Explore related vacuum circuit breakers for medium-voltage power distribution and protection applications.