Vacuum Circuit Breakers / 11 kV VCB Breaker
Baocheng Electrical · Technical review draft
11 kV VCB Breaker
ZW32-12
Intelligent outdoor vacuum switching for distribution feeders. The ZW32-12 combines a spring-operated breaker with current sensing and a protection controller for load switching, fault interruption and configurable automatic reclosing.
12 kV · 1250 A · 25 kA | Outdoor vacuum switching

Electrical Characteristics
Nominal system voltage
11 kV (confirm for the selected configuration)
Rated voltage
12 kV
Rated normal current
1250 A
Rated short-circuit breaking current
25 kA
About the ZW32-12
The supplied manual describes a 12 kV rated outdoor vacuum circuit breaker for three-phase 50 Hz distribution networks. Its controller supports phase overcurrent and earth-fault protection, with communication options to suit the feeder automation scheme.
The product-range title is 11 kV VCB Breaker; the equipment rated voltage in this manual is 12 kV. Confirm suitability for the actual network voltage and earthing arrangement.
Technical review draft: the manual contains inconsistent auxiliary-voltage, environmental and short-time withstand entries. The selected unit requires an approved data sheet before ordering.
Technical Specifications — ZW32-12
Electrical ratings — manual pp. 5–6
| No. | Parameter | Unit | Value / condition |
|---|---|---|---|
| 1 | Rated voltage | kV | 12 |
| 2 | Rated normal current | A | 1250 |
| 3 | Rated frequency | Hz | 50 |
| 4 | Rated short-circuit breaking current | kA | 25 |
| 5 | Rated short-circuit making current | kA peak | 63 |
| 6 | Rated duration of short circuit | s | 4 |
| 7 | Short-time withstand current | kA | Conflicting entries: 20 / 25; confirm |
Insulation — manual p. 5
| No. | Parameter | Unit | Value / condition |
|---|---|---|---|
| 1 | Power-frequency withstand, dry / wet, phase to earth | kV | 42 / 34 |
| 2 | Power-frequency withstand, across open contacts | kV | 48 |
| 3 | Lightning impulse withstand, phase to earth | kV peak | 75 |
| 4 | Lightning impulse withstand, across open contacts | kV peak | 85 |
Mechanical characteristics — manual pp. 5–7
| No. | Parameter | Unit | Value / condition |
|---|---|---|---|
| 1 | Mechanical endurance | operations | 10000 |
| 2 | Closing time | ms | 20–45 |
| 3 | Opening time | ms | ≤ 40 |
| 4 | Main circuit resistance | μΩ | ≤ 120 |
| 5 | Operating mechanism | — | Spring stored-energy |
Protection and control — manual pp. 2–3, 13–14
| No. | Parameter | Unit | Value / condition |
|---|---|---|---|
| 1 | Protection functions | — | Phase overcurrent and earth fault |
| 2 | Automatic reclosing | — | Up to 3 attempts; configurable |
| 3 | Remote communication | — | Optional; confirm protocol and hardware |
| 4 | Controller and coil supply | — | Confirm selected variant; manual entries differ |
Service conditions — confirmation required
| No. | Parameter | Unit | Value / condition |
|---|---|---|---|
| 1 | Breaker altitude entry, p. 5 | m | ≤ 2500 |
| 2 | Controller altitude entry, p. 12 | m | ≤ 2000 |
| 3 | Complete assembly altitude | — | Subject to controller and insulation selection |
| 4 | Ambient temperature | — | Confirm; source table labels are inconsistent |
ZW32-12: Design & Operating Principle
Protection Controller — Manual View
FDR-2 controller photograph from manual p. 11.
Coordinate the controller, current transformers, control cable and breaker coils as one protection package.
01 Measure & Detect
Current inputs feed the controller for phase-fault and earth-fault detection. Protection settings must be coordinated with upstream and downstream devices.
02 Trip & Reclose
The controller issues a trip command to the spring-operated breaker. Automatic reclosing is configurable and depends on the selected protection scheme.
03 Interrupt in Vacuum
Contact separation establishes an arc inside the vacuum interrupter. The arc extinguishes at current zero and the contact gap recovers its dielectric strength.
Control Interface
The manual includes FDR-2 and FDR-2GP information. Confirm controller type, connector pinout and coil supply for the supplied unit.
Drawings & Installation Interfaces
Review the supplied drawings for the selected arrangement. Select an image to inspect the full-size original; confirm the approved project revision before installation.
General Arrangement — Front & Side Views
| Rated-voltage family: ZW32-12 |
| Drawing phase centres: 340 mm |
| Drawing height: 720 mm |
| Dimensions apply to this illustrated arrangement |
The manual drawing shows the breaker body and its mounting interface. Other dimensions appear elsewhere in the manual; use the approved project drawing for installation.
FDR-2GP — Controller Connections
| TA and LS connector interfaces |
| Current-transformer inputs shown |
| Closing and trip coils identified |
| Drawing shows a 220 V AC circuit |
Original controller connection diagram from the manual. Confirm the connector variant and auxiliary voltage against the delivered controller before making connections.
Applications, Features & Procurement Considerations
The supplied manual describes a 12 kV rated outdoor vacuum circuit breaker for three-phase 50 Hz distribution networks. Its controller supports phase overcurrent and earth-fault protection, with communication options to suit the feeder automation scheme.
Feeder Protection
Phase and earth-fault functions support selective protection when coordinated with the network.
Automatic Reclosing
Up to three configurable reclose attempts are described for the controller.
Current Sensing
Current-transformer selection must match the protection and measurement requirements.
Remote Monitoring
Wired or wireless communication is an option; confirm the required interface.
Spring Operation
The manual lists 10,000 mechanical operations for the breaker.
Technical Documents & Supply Scope
ZW32-12 Technical Documents
Request the technical package for the selected configuration:
- Approved electrical ratings and model designation.
- General arrangement and mounting drawings.
- Controller wiring and current/voltage sensing details.
- Installation and maintenance instructions.
Inspection & Test Documentation
Request model-specific routine test records and any type-test evidence required by the project. The supplied reference manual alone does not establish certification for the offered equipment.
Agree the applicable standards, editions and evidence with the supplier. Resolve the technical-review items before approving the final data sheet.
Supply Scope to Confirm
- Exact model, ratings and number of units.
- Operating mechanism and auxiliary supply.
- Current/voltage transformers and controller options.
- Disconnectors, supports, cables and accessories.
- Site conditions and approved installation interfaces.
Identify included and excluded equipment explicitly. Confirm that the supplied drawings and controller configuration correspond to the ordered unit.
Maintenance Planning
Prepare the inspection and maintenance plan using the instructions for the delivered assembly and its controller. Confirm operating duty, site exposure and access requirements with the supplier.
Send the network voltage, load current, prospective fault current, control supply, site conditions and required installation arrangement with your inquiry.
11 kV VCB Breaker FAQ
Is this an 11 kV or a 12 kV breaker?
11 kV is the product-range title. The supplied manual specifies a 12 kV equipment rating; network compatibility must be confirmed for the project.
What current rating is used on this page?
The manual lists 1250 A and 25 kA short-circuit breaking current. The homepage lists a different normal current, so the offered configuration needs confirmation.
Does it support automatic reclosing?
The controller description provides up to three reclose attempts with configurable delays. The final scheme depends on the network protection study.
Is remote communication included?
Communication is configurable. Confirm the protocol, modem or wired interface and commissioning scope in the quotation.
Can the unit operate at 2500 m?
The breaker table lists 2500 m, while the controller section lists 2000 m. Confirm the complete assembly rating for the site.
Which control voltage should be ordered?
The manual contains different supply and coil-voltage entries. Specify the available auxiliary supply and obtain the matching approved wiring diagram.