Medium Voltage Equipment / 33 kV Switchgear
Baocheng Electrical
33 kV Switchgear
XGN15-36
Fixed air-insulated ring main units for ring and radial distribution. The 36 kV catalogue variant provides load switching and switch-fuse circuit options for the selected network scheme.
33 kV nominal system · 36 kV equipment class
630 A · 50 Hz
Air-insulated fixed RMU
What Is The XGN15-36?
XGN15 is a fixed air-insulated ring main unit family. The catalogue describes ring and radial supply applications, including prefabricated substations and power distribution control and protection.
The cabinet uses air insulation, while the described switching arrangement employs an SF₆ load-break switch or a switch-fuse combination. This is distinct from the XGN43 sealed gas-insulated RMU supplied in the other 33 kV document.
The 36 kV column is used throughout this page. The catalogue also includes 12 / 24 kV examples; their component models, dimensions and fault ratings must not be treated as confirmed 36 kV selections.
Technical Specification Tables
Table 1 — 36 kV electrical ratings
| Parameter | Value |
|---|---|
| Equipment rated voltage | 36 kV |
| Rated current / frequency | 630 A / 50 Hz |
| Short-time withstand current | 16 kA / 1 s |
| Peak withstand current | 40 kA peak |
| Short-circuit making current | 40 kA peak |
| Transfer current (catalogue designation) | 630 A |
| Closed-loop breaking current | 630 A |
| Maximum rated fuse current | 63 A |
Source: PDF page 2, printed page 034, 36 kV column. The source does not specify a circuit-breaker short-circuit breaking rating for this RMU.
Table 2 — Insulation, endurance & enclosure
| Parameter | 36 kV column |
|---|---|
| Power-frequency withstand, 1 min — phase / earth | 70 kV |
| Power-frequency withstand — isolating distance | 80 kV |
| Lightning impulse withstand — phase / earth | 170 kV peak |
| Lightning impulse withstand — isolating distance | 195 kV peak |
| Main switch mechanical class / operations | M1 / 1,000 |
| Earthing switch mechanical class / operations | M0 / 1,000 |
| Electrical endurance class | E3 |
| Internal-arc classification listed in catalogue | A-FLR 16 kA / 1 s |
| Degree of protection | IP4X |
Catalogue classifications are not evidence that a supplied project assembly has been tested to them. Obtain the matching type-test reports and confirm installation conditions.
Table 3 — Service conditions
| Parameter | Value |
|---|---|
| Ambient temperature | −15 to +40 °C |
| Altitude | ≤1,000 m |
| Relative humidity — daily / monthly mean | ≤95% / ≤90% |
| Water vapour pressure — daily / monthly mean | ≤2.2 / ≤1.8 kPa |
Indoor installation without significant pollution or combustible gases; special site conditions require agreement.
XGN15-36: Design & Operating Principle
Functional Overview
This diagram supports the operating description. It is not an approved primary schematic or switching procedure.
01 · Primary connection
The busbar system connects the selected ring, radial or transformer circuit. Cabinet and switch ratings are selected for the project voltage.
02 · Switching & fuse protection
The catalogue describes a load-break switch or a switch-fuse combination. Confirm the 36 kV switching device and fuse coordination; 12 kV device references are not transferred.
03 · Compartment interfaces
The busbar, switch, instrument and cable spaces organise primary and secondary interfaces. Operating access and pressure-relief arrangements require the approved layout.
General Arrangement & Installation Interfaces
Catalogue Cabinet Arrangement
| Item | Details |
|---|---|
| Depicted spaces | Busbar, switch, instruments, mechanism, cable |
| 36 kV dimensional applicability | Not confirmed |
Illustrative example / 示例图: the source does not assign this dimensional view to a verified 36 kV configuration. It explains the cabinet compartments only.
Catalogue Installation Interfaces
| Item | Details |
|---|---|
| Depicted interfaces | Aisle, cable duct and fixing points |
| 36 kV dimensional applicability | Not confirmed |
Illustrative example / 示例图: the source does not identify this dimensional sheet as a verified 36 kV installation drawing. Dimensions are retained only within the original reference image.
Applications, Features & Procurement Considerations
Fixed construction
An aluminium-zinc-coated steel cabinet with modular construction is described in the catalogue.
Ring & radial systems
Circuit functions can support ring supply, radial supply and transformer connections according to the chosen primary scheme.
Instrument compartment
The upper instrument compartment accommodates the specified meters, indicators and operating controls.
Installation planning
Confirm cable access, relief direction and aisle space against the project-specific 36 kV general arrangement.
Technical Documents & Supply Scope
XGN15-36 Technical Documents
Original supplied product document, with ratings, configuration information and available drawings. The original source language and annotations are retained.
Inspection & Test Documentation
The catalogue cites GB 3906, GB/T 11022, IEC 298 and DL/T 404. These historical references are not a certification claim; confirm the applicable editions and project test documents.
Supply Scope To Confirm
36 kV switching device; primary scheme; rated current and short-time duty; fuse-links and coordination; CT / VT quantities; earthing switches; auxiliary supply; cable interfaces; enclosure arrangement.
Maintenance Planning
Agree inspection intervals for mechanisms, interlocks, cable terminations and the selected SF₆ switching device. Use its approved operating manual.
33 kV Switchgear FAQ
No. This document describes XGN15 fixed air-insulated RMU construction. Its switching device may contain SF₆, but the cabinet insulation arrangement differs from XGN43 GIS.
The selected column lists 630 A, 16 kA for 1 s short-time withstand, and 40 kA peak withstand / making current.
No. It is the short-time withstand rating. A circuit-breaker short-circuit breaking duty is not specified for this configuration.
No. The front photograph shows a 24 kV sample and the series dimensional sheet is not expressly assigned to 36 kV. They are illustrative references only.
The 36 kV column lists a maximum rated fuse current of 63 A. Final fuse selection and transformer coordination require confirmation.
Related Products
Explore related medium-voltage switchgear and motor starting equipment for power distribution and industrial applications.