Home / Drop Out Fuses / 200 A Fuse Cutout
Baocheng Electrical
200 A Fuse Cutout
HRW11-10/200
The HRW11-10/200 is a 10 kV outdoor expulsion fuse cutout with a composite insulating support. Its 200 A configuration has a breaking current of 8.0 kA for overhead line and transformer protection.
10 kV rated voltage · 50 Hz system
200 A rated current · 8.0 kA breaking current
110 kV BIL · 42 kV power-frequency withstand voltage

Electrical Characteristics
Rated voltage
10 kV
Rated current
200 A
Breaking current
8.0 kA
System frequency
50 Hz
What Is the 200 A Fuse Cutout?
The cutout protects lines and transformers against overloads and short circuits. Its base supports the contacts and arc-extinguishing assembly.
A rotating spring support at the lower end keeps the fuse link under tension and helps retain the fuse tube in its closed position.
The HRW11-10 series includes two current ratings. Use the /200 row when specifying the 200 A cutout.
Technical Specifications & Selection Data
| Parameter or model | Unit | Value |
|---|---|---|
| HRW11-10/200 electrical ratings | ||
| Rated voltage | kV | 10 |
| Rated current | A | 200 |
| Breaking current | kA | 8.0 |
| Basic lightning impulse insulation level (BIL) | kV | 110 |
| Power-frequency withstand voltage | kV | 42 |
| HRW11-10 series comparison — rated current / breaking current | ||
| HRW11-10/100 | A / kA | 100 / 6.3 |
| HRW11-10/200 | A / kA | 200 / 8.0 |
| Outdoor service conditions | ||
| System frequency | Hz | 50 |
| Ambient temperature | °C | −30 to +40 |
| Maximum altitude | m | 1000 |
| Maximum wind speed | m/s | 35 |
The comparison gives cutout rated current followed by breaking current. Both configurations have a rated voltage of 10 kV, a BIL of 110 kV and a power-frequency withstand voltage of 42 kV.
Design & Operating Principle
Reading the Model Designation
![]() | ||
![]() | Rated current (A) | |
![]() | Rated voltage (kV) | |
![]() | Design series | |
![]() | Outdoor service | |
![]() | Fuse | |
![]() | Composite insulating support |
HRW11-10/200 · Model designation
The H prefix identifies a composite insulating support. The designation without H indicates a porcelain support.
Closed position
The lower spring support maintains tension on the fuse link.
Fuse operation
During an overload or short circuit, the fuse element melts and the link is rapidly withdrawn from the tube.
Arc extinction
The tube uses staged venting to interrupt currents of different magnitudes.
Load-switching duty
The family overview mentions switching rated load current. Obtain the applicable switching rating and operating instructions for the ordered configuration.
Outline & Mounting Drawings
The four outlines are grouped as they appear in the supplied drawing. Confirm the applicable outline and units for the ordered assembly.
Outline Drawings — Upper Pair
| Left outline: height 460 |
| Left outline: width 383 ± 2 |
| Right outline: height 555, width 470 |
The upper pair includes mounting-hole details beside each outline.
Outline Drawings — Lower Pair
| Left outline: height 465, width 385 |
| Right outline: height 540, width 465 |
| Mounting holes: 2 × Ø12 |
The document does not assign the four outlines to individual current ratings. Verify the mounting arrangement against the approved drawing.
Applications, Features & Selection Considerations
Check the installation site against the service limits before selecting the cutout.
Line protection
Overload and short-circuit protection for overhead lines.
Transformer protection
Select the fuse link to coordinate with the protected transformer.
Composite support
The H prefix identifies the support material.
Mechanical environment
Use in locations free from severe vibration or impact.
Atmospheric conditions
Exclude fire or explosion hazards, chemically aggressive gases, heavy atmospheric pollution and salt mist.
Technical Documents & Supply Scope
200 A Fuse Cutout Technical Documents
Request the technical package for the selected configuration:
- Model-specific data sheet
- Mounting and terminal drawing
- Fuse-link characteristics
Inspection & Test Documentation
Request the approved data sheet, insulation and breaking-duty test evidence, and inspection records for the exact cutout and fuse-link combination. Check the tested model, configuration and report scope.
Request the applicable insulation and breaking-current test reports for HRW11-10/200.
Supply Scope to Confirm
- HRW11-10/200 cutout quantity
- Fuse-link selection and spares
- Mounting hardware and terminals
Confirm accessories and quantities in the quotation.
Installation & Maintenance Review
Verify mounting dimensions, terminal connections and service clearances against the approved installation drawing.
Send the network voltage and earthing arrangement, required cutout rating, load and fault current, fuse-link requirements, site conditions, mounting details and quantity with your inquiry.
200 A Fuse Cutout FAQ
What voltage is the /200 model rated for?
The model table lists 10 kV.
What is the breaking current?
The 200 A version is rated at 8.0 kA. The 100 A version is rated at 6.3 kA.
What does H identify?
A composite insulating support.
What insulation levels are listed?
The table gives 110 kV BIL and 42 kV power-frequency withstand voltage.
What are the altitude and wind limits?
The maximum altitude is 1000 m and the maximum wind speed is 35 m/s.
What is the ambient temperature range?
The service range is −30 °C to +40 °C.
Related Products
Explore related drop out fuses and fuse cutouts for overhead distribution and transformer protection applications.