Home / Drop Out Fuses / 200 A Fuse Cutout

Baocheng Electrical

200 A Fuse Cutout
HRW11-10/200

The HRW11-10/200 is a 10 kV outdoor expulsion fuse cutout with a composite insulating support. Its 200 A configuration has a breaking current of 8.0 kA for overhead line and transformer protection.

10 kV rated voltage · 50 Hz system

200 A rated current · 8.0 kA breaking current

110 kV BIL · 42 kV power-frequency withstand voltage

cut out 200 amp

Electrical Characteristics

Rated voltage

10 kV

Rated current

200 A

Breaking current

8.0 kA

System frequency

50 Hz

What Is the 200 A Fuse Cutout?

The cutout protects lines and transformers against overloads and short circuits. Its base supports the contacts and arc-extinguishing assembly.

A rotating spring support at the lower end keeps the fuse link under tension and helps retain the fuse tube in its closed position.

The HRW11-10 series includes two current ratings. Use the /200 row when specifying the 200 A cutout.

Technical Specifications & Selection Data

Parameter or modelUnitValue
HRW11-10/200 electrical ratings
Rated voltagekV10
Rated currentA200
Breaking currentkA8.0
Basic lightning impulse insulation level (BIL)kV110
Power-frequency withstand voltagekV42
HRW11-10 series comparison — rated current / breaking current
HRW11-10/100A / kA100 / 6.3
HRW11-10/200A / kA200 / 8.0
Outdoor service conditions
System frequencyHz50
Ambient temperature°C−30 to +40
Maximum altitudem1000
Maximum wind speedm/s35

The comparison gives cutout rated current followed by breaking current. Both configurations have a rated voltage of 10 kV, a BIL of 110 kV and a power-frequency withstand voltage of 42 kV.

Design & Operating Principle

Reading the Model Designation

H R W 11 10 200
Rated current (A)
Rated voltage (kV)
Design series
Outdoor service
Fuse
Composite insulating support

HRW11-10/200 · Model designation

The H prefix identifies a composite insulating support. The designation without H indicates a porcelain support.

Closed position

The lower spring support maintains tension on the fuse link.

Fuse operation

During an overload or short circuit, the fuse element melts and the link is rapidly withdrawn from the tube.

Arc extinction

The tube uses staged venting to interrupt currents of different magnitudes.

Load-switching duty

The family overview mentions switching rated load current. Obtain the applicable switching rating and operating instructions for the ordered configuration.

Outline & Mounting Drawings

The four outlines are grouped as they appear in the supplied drawing. Confirm the applicable outline and units for the ordered assembly.

Outline Drawings — Upper Pair

Left outline: height 460
Left outline: width 383 ± 2
Right outline: height 555, width 470

The upper pair includes mounting-hole details beside each outline.

Outline Drawings — Lower Pair

Left outline: height 465, width 385
Right outline: height 540, width 465
Mounting holes: 2 × Ø12

The document does not assign the four outlines to individual current ratings. Verify the mounting arrangement against the approved drawing.

Applications, Features & Selection Considerations

Check the installation site against the service limits before selecting the cutout.

Line protection

Overload and short-circuit protection for overhead lines.

Transformer protection

Select the fuse link to coordinate with the protected transformer.

Composite support

The H prefix identifies the support material.

Mechanical environment

Use in locations free from severe vibration or impact.

Atmospheric conditions

Exclude fire or explosion hazards, chemically aggressive gases, heavy atmospheric pollution and salt mist.

Technical Documents & Supply Scope

200 A Fuse Cutout Technical Documents

Request the technical package for the selected configuration:

  • Model-specific data sheet
  • Mounting and terminal drawing
  • Fuse-link characteristics

Inspection & Test Documentation

Request the approved data sheet, insulation and breaking-duty test evidence, and inspection records for the exact cutout and fuse-link combination. Check the tested model, configuration and report scope.

Request the applicable insulation and breaking-current test reports for HRW11-10/200.

Supply Scope to Confirm

  • HRW11-10/200 cutout quantity
  • Fuse-link selection and spares
  • Mounting hardware and terminals

Confirm accessories and quantities in the quotation.

Installation & Maintenance Review

Verify mounting dimensions, terminal connections and service clearances against the approved installation drawing.

Send the network voltage and earthing arrangement, required cutout rating, load and fault current, fuse-link requirements, site conditions, mounting details and quantity with your inquiry.

200 A Fuse Cutout FAQ

The model table lists 10 kV.

The 200 A version is rated at 8.0 kA. The 100 A version is rated at 6.3 kA.

A composite insulating support.

The table gives 110 kV BIL and 42 kV power-frequency withstand voltage.

The maximum altitude is 1000 m and the maximum wind speed is 35 m/s.

The service range is −30 °C to +40 °C.

Related Products

Explore related drop out fuses and fuse cutouts for overhead distribution and transformer protection applications.