Baocheng Electrical · DRAFT — Technical Verification Pending

Drop Out Fuse
33 kV Product Category

Outdoor drop-out fuse page prepared for the 33 kV product category. The supplied Eaton / Cooper Type L catalogue provides reference configurations; the offered Baocheng model and its applicable ratings remain to be verified.

DRAFT · 33 kV Product Verification Required

Reference Catalogue · Separate 38 / 40.5 kV Configurations

Outdoor Distribution · Model-Specific Selection

Electrical Characteristics

Nominal system voltage

33 kV 

Requested voltage category

33 kV

Offered equipment rating

To be confirmed

Current / breaking duty

To be confirmed

What Is the Drop Out Fuse?

Expulsion fuse cutouts are used for overcurrent protection of suitable overhead distribution circuits. Selection requires the system voltage, earthing arrangement, insulation level, continuous current, available fault current and a coordinated fuse link.

Draft — product mapping pending. The supplied document is an Eaton / Cooper Type L catalogue. Its higher-voltage table lists a 40.5 kV polymeric configuration and a 38 kV porcelain configuration. Neither is automatically a verified rating of the requested Baocheng 33 kV product.

The two catalogue configurations have different breaking currents, insulation levels, creepage distances and altitude limits. They remain separate reference tables below. The 12 kV figures, certifications, interchangeability and load-switching claims elsewhere in the catalogue are not transferred to this product.

Technical Specifications & Selection Data

Table 1 — S9FAP1A — Eaton / Cooper Reference Only

No.ParameterUnitValue
01Insulation / catalogue model—Silicone rubber / S9FAP1A
02Rated voltagekV40.5
03Rated currentA100
04Rated frequencyHz50
05Rated short-circuit breaking currentkA6
06Power-frequency withstand, dry / wetkV108 / 91
07Power-frequency withstand across isolating distance, dry / wetkV134 / 109
08Lightning impulse withstand, to earth / across isolating distancekV210 / 243
09Mechanical enduranceoperations1000
10Altitude limitm2000
11TRV class—B
12Creepage distancemm1256

Table 2 — L9EAP1A — Eaton / Cooper Reference Only

No.ParameterUnitValue
01Insulation / catalogue model—Porcelain / L9EAP1A
02Rated voltagekV38
03Rated currentA100
04Rated frequencyHz50
05Rated short-circuit breaking currentkA8
06Power-frequency withstand, dry / wetkV70 / 60
07Power-frequency withstand across isolating distance, dry / wetkV80 / 60
08Lightning impulse withstand, to earth / across isolating distancekV170 / 200
09Mechanical enduranceoperations200
10Altitude limitm1000
11TRV class—B
12Creepage distancemm720

Source: supplied Eaton / Cooper Type L catalogue, PDF page 9 (printed page 6). These are third-party reference ratings, not Baocheng product specifications. The catalogue installation drawings on PDF pages 10–11 are expressly for 12 kV and are not used as 33 kV mounting drawings.

Table 3 — 33 kV Product — Outstanding Verification

No.ParameterUnitValue
01Offered Baocheng model—To be confirmed
02Equipment rated voltagekVTo be confirmed against the network maximum voltage
03Rated current and breaking duty—To be confirmed for the offered model
04Mounting dimensions—No verified high-voltage installation drawing supplied
05Service conditions and test evidence—To be confirmed; reference catalogue limits are model-specific

Drop-Out Fuse: General Arrangement & Operation

Type L Reference Assembly

Illustrative example / 示例图 — Eaton / Cooper catalogue, PDF page 6, Figure 3. This is not a verified 33 kV product structure.

The reference labels the upper terminal, protective hood, contacts, operating ring, fuseholder, hinge, lower terminal and mounting bracket. Insulator form and dimensions depend on the selected model.

01 Coordinated Fuse Link

The fuse link carries normal load current. Its time-current characteristic must coordinate with transformer inrush, feeder loading and adjacent protective devices.

02 Expulsion Interruption

An arc-extinguishing lining generates gas during fuse operation to assist interruption. The cutout, fuseholder and fuse link must form the tested combination for the required fault duty.

03 Visible Open Position

The hinged fuseholder drops after operation. Load-current switching, tool compatibility and restoration procedures require confirmation for the actual offered equipment.

Model-Specific Load-Switching Duty

The catalogue contains both standard and load-break designs. The high-voltage reference table is labelled standard type; the 12 kV load-switching endurance figures must not be applied to these higher-voltage configurations.

Reference Assembly & Fuse-Link Construction

The figures below explain the reference construction only. A confirmed outline and installation drawing for the offered 33 kV-category product is still required.

Type L Assembly — Reference Example

Illustrative example / 示例图
Eaton / Cooper Figure 3, PDF page 6
Main terminal, insulator and fuseholder labels
Not a verified 33 kV mounting drawing

The original Chinese labels are preserved. This reference explains component relationships only; it does not establish the construction or dimensional interfaces of the offered Baocheng model.

Fuse Link — Reference Construction

Illustrative example / 示例图
Eaton / Cooper Figure 4, PDF page 6
Fuse element, auxiliary tube and flexible lead
No dimensions or compatibility rating inferred

The reference shows a fuse element, tension member, connection terminal, auxiliary arc-extinguishing tube and lead. Select the actual fuse link using the approved compatibility and time-current data.

Applications, Features & Selection Considerations

Prepare the following information for a 33 kV-category equipment selection. Confirm each item against the final offered model rather than choosing a rating from the category title alone.

Voltage & Earthing

Check maximum voltage across the fuse and system earthing.

Insulation Coordination

Compare impulse levels and creepage with the installation.

Fault Duty

Keep each model’s rated breaking current distinct.

Fuse-Link Selection

Coordinate load, inrush and protection characteristics.

Site & Mounting

Confirm altitude, environment, bracket and terminals.

Technical Documents & Supply Scope

Drop Out Fuse Technical Documents

Request the technical package for the selected configuration:

  • Confirmed Baocheng model and approved electrical data sheet.
  • Applicable type-test evidence for that exact configuration.
  • High-voltage outline, mounting and terminal drawings.
  • Fuse-link curves, compatibility and operating instructions.

Inspection & Test Documentation

Request the approved data sheet, insulation and breaking-duty test evidence, and inspection records for the exact cutout and fuse-link combination. Check the tested model, configuration and report scope.

The catalogue contains Eaton / Cooper certification and interchangeability statements, including 12 kV test references. They are not evidence for the offered Baocheng product and are not claimed as its approvals.

Supply Scope to Confirm

  • Exact offered model and equipment rated voltage.
  • Insulator material, rated current and breaking duty.
  • Compatible fuse links and required spare quantity.
  • Terminals, brackets and operating-tool requirements.
  • Approved inspection documents, quantity and delivery scope.

Reference catalogue accessories and brands are not treated as the agreed Baocheng supply scope. Confirm every included item in the technical quotation.

Installation & Maintenance Review

The supplied dimensional tables cover 12 kV equipment. A matching high-voltage installation drawing is needed before deciding mounting holes, phase clearances or operating space for the requested 33 kV-category unit.

Send the network voltage and earthing arrangement, required cutout rating, load and fault current, fuse-link requirements, site conditions, mounting details and quantity with your inquiry.

Drop Out Fuse FAQ

Not by itself. It is the requested product-category title. The supplied third-party reference lists 38 kV and 40.5 kV high-voltage configurations; the offered model and equipment rating still require confirmation.

No. S9FAP1A is listed at 40.5 kV, 100 A and 6 kA; L9EAP1A is listed at 38 kV, 100 A and 8 kA. Their insulation, creepage, endurance and altitude limits also differ.

No. The tables are explicitly identified as Eaton / Cooper catalogue references. The source does not establish certification or rating equivalence for a Baocheng product.

The supplied installation drawings on PDF pages 10–11 are marked 12 kV. They have not been reused as 33 kV drawings. Obtain the approved drawing for the offered unit.

The precise configuration and operating method must be confirmed. Load-switching figures for the catalogue’s 12 kV load-break versions are not ratings for the high-voltage standard-type models.

Provide the offered model, system maximum voltage and earthing, load and fault duty, insulation requirements, fuse-link characteristic, site conditions, mounting details and quantity.

Related Products

Explore related drop out fuses and fuse cutouts for overhead distribution and transformer protection applications.