SF6 Circuit Breakers / 72.5 kV SF6 Circuit Breaker
Baocheng Electrical
72.5 kV SF6 Circuit Breaker — LW36-72.5
Outdoor three-phase switching and protection for 66 kV nominal-system projects, with a 72.5 kV equipment rating and a CTB-1 spring operating mechanism.
LW36-72.5 — 72.5 kV Rated Voltage
For 66 kV nominal-system projects
3150 A · 40 kA · Outdoor

Electrical Characteristics
66 kV
Nominal system voltage
Equipment rated voltage
72.5 kV
Continuous current
3150 A
Short-circuit breaking current
40 kA
Product Overview
The LW36-72.5 is an outdoor SF6 circuit breaker with three poles and one interrupter per phase. It combines SF6 insulation and arc interruption with a common spring-operated drive for three-phase switching.
The supplied manual lists a rated voltage of 72.5 kV, a rated continuous current of 3150 A and a rated short-circuit breaking current of 40 kA. These equipment ratings are kept separate from the nominal voltage used to describe the power system.
Use the 66 kV nominal system as the principal selection basis for this page. Final suitability depends on the project’s maximum operating voltage, insulation coordination, frequency, short-circuit duty and service conditions.
Nominal System Voltage and Equipment Rating
Nominal system voltage
Equipment rated voltage
Selection status
66 kV
72.5 kV
Primary selection basis; confirm maximum system voltage, insulation levels and duty.
69 kV
72.5 kV
Project review only; frequency, insulation, fault duty and applicable standard must be confirmed.
69 kV is a project-review option, not an additional confirmed product rating. The supplied manual specifies 50 Hz; 60 Hz service is not confirmed by this manual.
LW36-72.5KV — Technical Specifications
Swipe horizontally to view all specifications.
| No. | Item | Unit | Technical Parameters | |
|---|---|---|---|---|
| 01 | Rated voltage | kV | 72.5 | |
| 02 | Rated frequency | Hz | 50 | |
| 03 | Rated current | A | 3150 | |
| 04 | Rated short-circuit breaking current | Short-circuit current | kA | 40 |
| DC component | — | 40% | ||
| 05 | Rated duration of short circuit | s | 4 | |
| 06 | Rated short-time withstand current | kA | 40 | |
| 07 | Rated short-circuit making current (peak) | kA | 100 | |
| 08 | Rated peak withstand current | 100 | ||
| 09 | Rated 1 min power-frequency withstand voltage (r.m.s.) | Phase-to-earth and phase-to-phase | kV | 160 |
| Across open contacts | 200 | |||
| 10 | Rated lightning impulse withstand voltage (peak) | Phase-to-earth and phase-to-phase | 380 | |
| Across open contacts | 410 | |||
| 11 | 5 min withstand voltage at zero gauge pressure (r.m.s.) | Across open contacts and phase-to-earth | 95 | |
| 12 | Rated out-of-phase breaking current | kA | 10 | |
| 13 | Short-line fault breaking current | IeX90%,IeX75% | ||
| 14 | Rated line-charging breaking current | A | 50 | |
| 15 | Rated operating sequence | — | O–0.3 s–CO–180 s–CO | |
| 16 | First-pole-to-clear factor | — | 1.5 | |
| 17 | Closing time | ms | ≤100 | |
| 18 | Opening time | ≤50 | ||
| 19 | Break time | ≤50 | ||
| 20 | Close-open time | ≤60 | ||
| 21 | Opening synchronism | ≤3 | ||
| 22 | Closing synchronism | ≤5 | ||
| 23 | Rated SF6 gas pressure (20°C) | MPa | 0.5 | |
| 24 | Annual SF6 gas leakage rate | — | ≤0.5% | |
| 25 | Gas moisture content | ppm (v/v) | ≤150 | |
| 26 | Radio interference level | μV | ≤2500 | |
| 27 | Mechanical life | operations | 20000 | |
| 28 | Mass per circuit breaker | kg | 1400 | |
| 29 | SF6 gas filling mass per circuit breaker | 8 | ||
| 30 | Main circuit resistance per pole | μΩ | 70 | |
LW36-72.5KV — Mechanical Parameters
Swipe horizontally to view all specifications.
| No. | Item | Unit | Data | Remarks |
|---|---|---|---|---|
| 01 | Moving contact travel | mm | 130±2 | |
| 02 | Contact travel | 35±5 | ||
| 03 | Spring mechanism travel | 1000−3 | ||
| 04 | Clearance between crank-arm roller and mechanical cam | 1.4±0.3 | Circuit breaker open; closing spring charged | |
| 05 | Distance B between closing spring positioning nut and positioning rod | 12~47 | ||
| 06 | Closing electromagnet travel C | 5.0~5.5 | Circuit breaker open | |
| Clearance D between trigger and release | 2.0~2.5 | |||
| C−D | 3.0~3.5 | |||
| 07 | Opening electromagnet travel F | 2.8~3.2 | Circuit breaker closed | |
| Clearance G between trigger and release | 0.8~1.2 | |||
| F−G | 1.6~2.4 |
LW36-72.5KV — Control and Auxiliary Circuit Parameters
Swipe horizontally to view all specifications.
| No. | Item | Unit | Parameters | ||
|---|---|---|---|---|---|
| 01 | Opening and closing circuit control voltage | V | 220 DC | 110 DC | |
| 02 | Opening coil current | A | <2.3 | 5.5 | |
| 03 | Closing coil current | A | 2 | 3.5 | |
| 04 | Energy storage motor | Supply voltage | V | 220 (110) DC / 220 AC | |
| Normal operating voltage range | — | 65%~110% | |||
| Power | W | 450 | |||
| Energy storage time | s | ≤15 | |||
| Speed | r.p.m | 750 | |||
| Current | A | 3.6 | 5.5 | ||
| 05 | Heater and lighting circuit voltage | V | 220 AC | ||
| 06 | Heater power | W | 100 | ||
LW36-72.5KV — SF6 Gas Pressure Parameters (20°C)
Swipe horizontally to view all specifications.
| No. | Item | Unit | Parameters |
|---|---|---|---|
| 01 | Rated filling pressure | MPa | 0.5 |
| 02 | Gas replenishment alarm pressure | 0.45±0.03 | |
| 03 | Lockout pressure | 0.40±0.03 |
Construction and Working Principle
Three-phase arrangement
Three single-break poles are supported on a common frame and operated through a common spring mechanism.
SF6 arc interruption
The manual describes thermal expansion with assisted gas blowing to interrupt the arc during opening.
Spring operating mechanism
The CTB-1 mechanism stores mechanical energy for closing and opening operations. Match the auxiliary supply and control arrangement to the project.
Gas supervision
The manual provides separate SF6 refill-alarm and lockout settings for supervision of the gas condition.
General Arrangement and Connection Details
General Arrangement

Source: supplied manual, PDF page 8.
Check the approved overall dimensions, phase spacing and foundation interfaces before installation.
Terminal and Foundation Details

Source: supplied manual, PDF page 9.
Side view, terminal connection and foundation details in the supplied manual.
Applications and Service Conditions
Consider the LW36-72.5 for outdoor substation switching and protection duties on 66 kV nominal systems. Line bays, transformer bays and bus-coupling duties require project-specific checks of fault level, switching duty and insulation coordination.
For industrial receiving substations or renewable-generation grid connections, assess the same electrical and site requirements before selecting the breaker. The system’s nominal voltage alone does not determine suitability.
Parameter
Value
Ambient air temperature
−30°C to +40°C
Special low-temperature condition in the manual
−40°C to +40°C — confirm the supplied configuration
Altitude limit listed in the manual
≤4500 m — confirm insulation coordination for the installation altitude
Relative humidity, daily / monthly average
≤95% / ≤90% (at 25°C)
Wind pressure
≤700 Pa
Ice thickness
10 mm
Seismic acceleration, horizontal / vertical
≤0.3g / ≤0.15g
Maximum daily temperature variation
25°C
Nominal creepage distance
31 mm/kV
The altitude and special temperature limits are manual entries, not a statement that every supplied configuration meets every extreme condition simultaneously. Confirm site pollution, creepage, altitude corrections and the required low-temperature arrangement.
Features and Practical Benefits
3150 A continuous-current rating
A clearly defined current rating for load and busbar coordination.
40 kA short-circuit breaking rating
A stated fault-interruption rating to compare with the project fault study.
Separate insulation ratings
Power-frequency and lightning-impulse levels are listed separately for phase-to-earth and open-contact duties.
Spring-operated drive
The CTB-1 mechanism and specified auxiliary supplies provide a basis for control-system coordination.
Defined gas supervision settings
Refill-alarm and lockout values can be reviewed alongside the site’s alarm and interlocking requirements.
Technical Documents and Supply Scope
The supplied manual includes technical parameters, arrangement drawings, operating-mechanism information and electrical diagrams. Use project-approved documents for installation and commissioning.
Documents to Agree for the Order
- Guaranteed technical particulars for the selected voltage, current, frequency and switching duties.
- Approved general arrangement, foundation and terminal connection drawings.
- Control schematic, terminal schedule and auxiliary-supply requirements.
- Applicable inspection and test documents, instruction manual and packing list.
Supply Scope to Confirm
Agree the breaker assembly, operating mechanism, supporting structure, terminal connectors, accessories, spare parts and document package in the quotation. Inclusion of individual items is subject to the order.
The manuals reference GB 1984-2003 and IEC 62271-100:2001. These references identify the editions cited by the manuals; they do not establish certification to a current edition. Confirm the required standard and supporting test evidence for the project.
Technical and Purchasing FAQ
Is 72.5 kV the nominal system voltage?
No. 72.5 kV is the equipment rated voltage in the manual. This page uses 66 kV as the primary nominal-system selection basis, subject to project coordination.
Can the breaker be considered for a 69 kV system?
Only after a project-specific review. Confirm the maximum system voltage, required insulation levels, frequency, fault duty and applicable standards. The 69 kV entry is not a confirmed alternative rating.
What current and breaking ratings are listed?
The model-specific manual lists 3150 A rated continuous current and 40 kA rated short-circuit breaking current. These values should be reproduced in the final guaranteed technical particulars.
Which operating mechanism is used?
The manual specifies the CTB-1 spring operating mechanism. Confirm the control supply, charging-motor supply and secondary wiring for the order.
Can the manual drawings be used directly for installation?
Use approved drawings for the ordered configuration. The reproduced drawings are manual references; foundation interfaces, terminal details and final dimensions require project confirmation.
What information is needed for a quotation?
Provide the nominal and maximum system voltage, frequency, continuous current, fault level, insulation requirements, site altitude and temperature, auxiliary supplies, required quantity and applicable standard.
Discuss Your 66 kV System Requirements
Send your project specification for the LW36-72.5. Include the nominal and maximum system voltage, frequency, fault duty, insulation requirements and site conditions so that the offered configuration can be checked.
Related SF6 Circuit Breakers
12 kV rated · 630 A · 20 kA
Pole-mounted switching for 6/10/11 kV systems. Review the LW6-12 configuration and installation requirements.
40.5 kV rated · 1600 A · 31.5 kA
LW8-40.5(T) for 33 kV systems. Compare the operating duty, insulation level and project requirements.
40.5 kV rated · 2000 A · 40 kA
Outdoor LW8-40.5Y for 35 kV systems. Confirm the supplied configuration and installation conditions.
126 kV rated · 3150 A · 40 kA
LW36-126 for 110 kV system projects. Confirm system voltage, insulation requirements and site conditions.
40.5 kV rated · 1250 A · 25 kA
Indoor SFM-40.5 configuration for 35 kV systems. Check the switchgear arrangement and installation dimensions.