SF6 Circuit Breakers / 72.5 kV SF6 Circuit Breaker

Baocheng Electrical

72.5 kV SF6 Circuit Breaker — LW36-72.5

Outdoor three-phase switching and protection for 66 kV nominal-system projects, with a 72.5 kV equipment rating and a CTB-1 spring operating mechanism.

LW36-72.5 — 72.5 kV Rated Voltage

For 66 kV nominal-system projects
3150 A · 40 kA · Outdoor

sf6 gas circuit breaker

Electrical Characteristics

66 kV

Nominal system voltage

Equipment rated voltage

72.5 kV

Continuous current

3150 A

Short-circuit breaking current

40 kA

Product Overview

The LW36-72.5 is an outdoor SF6 circuit breaker with three poles and one interrupter per phase. It combines SF6 insulation and arc interruption with a common spring-operated drive for three-phase switching.

The supplied manual lists a rated voltage of 72.5 kV, a rated continuous current of 3150 A and a rated short-circuit breaking current of 40 kA. These equipment ratings are kept separate from the nominal voltage used to describe the power system.

Use the 66 kV nominal system as the principal selection basis for this page. Final suitability depends on the project’s maximum operating voltage, insulation coordination, frequency, short-circuit duty and service conditions.

Nominal System Voltage and Equipment Rating

Nominal system voltage

Equipment rated voltage

Selection status

66 kV

72.5 kV

Primary selection basis; confirm maximum system voltage, insulation levels and duty.

69 kV

72.5 kV

Project review only; frequency, insulation, fault duty and applicable standard must be confirmed.

69 kV is a project-review option, not an additional confirmed product rating. The supplied manual specifies 50 Hz; 60 Hz service is not confirmed by this manual.

LW36-72.5KV — Technical Specifications

Swipe horizontally to view all specifications.

No.ItemUnitTechnical Parameters
01Rated voltagekV72.5
02Rated frequencyHz50
03Rated currentA3150
04Rated short-circuit breaking currentShort-circuit currentkA40
DC component—40%
05Rated duration of short circuits4
06Rated short-time withstand currentkA40
07Rated short-circuit making current (peak)kA100
08Rated peak withstand current100
09Rated 1 min power-frequency withstand voltage (r.m.s.)Phase-to-earth and phase-to-phasekV160
Across open contacts200
10Rated lightning impulse withstand voltage (peak)Phase-to-earth and phase-to-phase380
Across open contacts410
115 min withstand voltage at zero gauge pressure (r.m.s.)Across open contacts and phase-to-earth95
12Rated out-of-phase breaking currentkA10
13Short-line fault breaking currentIeX90%,IeX75%
14Rated line-charging breaking currentA50
15Rated operating sequence—O–0.3 s–CO–180 s–CO
16First-pole-to-clear factor—1.5
17Closing timems≤100
18Opening time≤50
19Break time≤50
20Close-open time≤60
21Opening synchronism≤3
22Closing synchronism≤5
23Rated SF6 gas pressure (20°C)MPa0.5
24Annual SF6 gas leakage rate—≤0.5%
25Gas moisture contentppm (v/v)≤150
26Radio interference levelμV≤2500
27Mechanical lifeoperations20000
28Mass per circuit breakerkg1400
29SF6 gas filling mass per circuit breaker8
30Main circuit resistance per poleμΩ70

LW36-72.5KV — Mechanical Parameters

Swipe horizontally to view all specifications.

No.ItemUnitDataRemarks
01Moving contact travelmm130±2
02Contact travel35±5
03Spring mechanism travel1000−3
04Clearance between crank-arm roller and mechanical cam1.4±0.3Circuit breaker open; closing spring charged
05Distance B between closing spring positioning nut and positioning rod12~47
06Closing electromagnet travel C5.0~5.5Circuit breaker open
Clearance D between trigger and release2.0~2.5
C−D3.0~3.5
07Opening electromagnet travel F2.8~3.2Circuit breaker closed
Clearance G between trigger and release0.8~1.2
F−G1.6~2.4

LW36-72.5KV — Control and Auxiliary Circuit Parameters

Swipe horizontally to view all specifications.

No.ItemUnitParameters
01Opening and closing circuit control voltageV220 DC110 DC
02Opening coil currentA<2.35.5
03Closing coil currentA23.5
04Energy storage motorSupply voltageV220 (110) DC / 220 AC
Normal operating voltage range—65%~110%
PowerW450
Energy storage times≤15
Speedr.p.m750
CurrentA3.65.5
05Heater and lighting circuit voltageV220 AC
06Heater powerW100

LW36-72.5KV — SF6 Gas Pressure Parameters (20°C)

Swipe horizontally to view all specifications.

No.ItemUnitParameters
01Rated filling pressureMPa0.5
02Gas replenishment alarm pressure0.45±0.03
03Lockout pressure0.40±0.03

Construction and Working Principle

Three-phase arrangement

Three single-break poles are supported on a common frame and operated through a common spring mechanism.

SF6 arc interruption

The manual describes thermal expansion with assisted gas blowing to interrupt the arc during opening.

Spring operating mechanism

The CTB-1 mechanism stores mechanical energy for closing and opening operations. Match the auxiliary supply and control arrangement to the project.

Gas supervision

The manual provides separate SF6 refill-alarm and lockout settings for supervision of the gas condition.

General Arrangement and Connection Details

General Arrangement

Source: supplied manual, PDF page 8.

Check the approved overall dimensions, phase spacing and foundation interfaces before installation.

Terminal and Foundation Details

Source: supplied manual, PDF page 9.

Side view, terminal connection and foundation details in the supplied manual.

Applications and Service Conditions

Consider the LW36-72.5 for outdoor substation switching and protection duties on 66 kV nominal systems. Line bays, transformer bays and bus-coupling duties require project-specific checks of fault level, switching duty and insulation coordination.

For industrial receiving substations or renewable-generation grid connections, assess the same electrical and site requirements before selecting the breaker. The system’s nominal voltage alone does not determine suitability.

Parameter

Value

Ambient air temperature

−30°C to +40°C

Special low-temperature condition in the manual

−40°C to +40°C — confirm the supplied configuration

Altitude limit listed in the manual

≤4500 m — confirm insulation coordination for the installation altitude

Relative humidity, daily / monthly average

≤95% / ≤90% (at 25°C)

Wind pressure

≤700 Pa

Ice thickness

10 mm

Seismic acceleration, horizontal / vertical

≤0.3g / ≤0.15g

Maximum daily temperature variation

25°C

Nominal creepage distance

31 mm/kV

The altitude and special temperature limits are manual entries, not a statement that every supplied configuration meets every extreme condition simultaneously. Confirm site pollution, creepage, altitude corrections and the required low-temperature arrangement.

Features and Practical Benefits

3150 A continuous-current rating

A clearly defined current rating for load and busbar coordination.

40 kA short-circuit breaking rating

A stated fault-interruption rating to compare with the project fault study.

Separate insulation ratings

Power-frequency and lightning-impulse levels are listed separately for phase-to-earth and open-contact duties.

Spring-operated drive

The CTB-1 mechanism and specified auxiliary supplies provide a basis for control-system coordination.

Defined gas supervision settings

Refill-alarm and lockout values can be reviewed alongside the site’s alarm and interlocking requirements.

Technical Documents and Supply Scope

The supplied manual includes technical parameters, arrangement drawings, operating-mechanism information and electrical diagrams. Use project-approved documents for installation and commissioning.

Documents to Agree for the Order

  • Guaranteed technical particulars for the selected voltage, current, frequency and switching duties.
  • Approved general arrangement, foundation and terminal connection drawings.
  • Control schematic, terminal schedule and auxiliary-supply requirements.
  • Applicable inspection and test documents, instruction manual and packing list.

Supply Scope to Confirm

Agree the breaker assembly, operating mechanism, supporting structure, terminal connectors, accessories, spare parts and document package in the quotation. Inclusion of individual items is subject to the order.

The manuals reference GB 1984-2003 and IEC 62271-100:2001. These references identify the editions cited by the manuals; they do not establish certification to a current edition. Confirm the required standard and supporting test evidence for the project.

Technical and Purchasing FAQ

Is 72.5 kV the nominal system voltage?

No. 72.5 kV is the equipment rated voltage in the manual. This page uses 66 kV as the primary nominal-system selection basis, subject to project coordination.

Can the breaker be considered for a 69 kV system?

Only after a project-specific review. Confirm the maximum system voltage, required insulation levels, frequency, fault duty and applicable standards. The 69 kV entry is not a confirmed alternative rating.

What current and breaking ratings are listed?

The model-specific manual lists 3150 A rated continuous current and 40 kA rated short-circuit breaking current. These values should be reproduced in the final guaranteed technical particulars.

Which operating mechanism is used?

The manual specifies the CTB-1 spring operating mechanism. Confirm the control supply, charging-motor supply and secondary wiring for the order.

Can the manual drawings be used directly for installation?

Use approved drawings for the ordered configuration. The reproduced drawings are manual references; foundation interfaces, terminal details and final dimensions require project confirmation.

What information is needed for a quotation?

Provide the nominal and maximum system voltage, frequency, continuous current, fault level, insulation requirements, site altitude and temperature, auxiliary supplies, required quantity and applicable standard.